WATER-DISTRICT ROUTE & ASSE 5110 WORKSPACE
Primary BPAT: Marcus Vance (BPAT-88412) · Test Kit: Mid-West 845-5 (#MW-99214)
Purveyor:
Assemblies on Route: 4 · Purveyor Districts: 2
District-Report Filing Queue
1 pendingTests passed on-site · Awaiting formal water purveyor submissionASSE PASSWatts 009 (S/N #W009-88124, 2" RPZ)
Cascade Plaza Commerce · Purveyor: City Water District #4 · Tested Oct 27, 2026 by Marcus Vance
Readings: Line 68 PSI · CK1 7.2 psid · CK2 2.1 psid · Relief 3.4 psid · Shutoff #2 Tight
Water-District Route & Assembly Roster
ASSE 5110 Evaluation Engine Active · 335-Day Retest Logic
City Water District #4 Route
3 valvesAnnual 335d Advance Retest RecallDCVAlow hazard
Ames 2000SS · Serial #AM-44910 · 4"
Cascade Plaza Commerce · 1200 Commercial Way, Portland · Fire riser room east corridor
District: City Water District #4 · Line Pressure: 65 PSI
Assigned Tester: Sarah Chen (BPAT-91024) · Kit: Watts TK-9A (#TK-44102)
LOCKED_GAUGE_EXPIREDLast Test: Not yet testedNext Due: Sep 27, 2027 (335-day recall)
Check #1 DifferentialFloor: 1.0 PSID
2.2 PSID
Check #2 DifferentialFloor: 1.0 PSID
2.0 PSID
Relief Valve OpeningFloor: 2.0 PSID
0.0 PSID
Tiered Fee: $125.00 ($125.00 >2" commercial)
🔒 Tester gauge calibration is expired (expired 2026-09-22). Cannot sign compliance report.
RPZhigh hazard
Watts 009 · Serial #W009-88124 · 2"
Cascade Plaza Commerce · 1200 Commercial Way, Portland · Main domestic water vault front parking lot
District: City Water District #4 · Line Pressure: 68 PSI
Assigned Tester: Marcus Vance (BPAT-88412) · Kit: Mid-West 845-5 (#MW-99214)
ASSE 5110 PASSLast Test: Oct 27, 2026Next Due: Sep 27, 2027 (335-day recall)
Check #1 DifferentialFloor: 5.0 PSID
7.2 PSID
Check #2 DifferentialFloor: 1.0 PSID
2.1 PSID
Relief Valve OpeningFloor: 2.0 PSID
3.4 PSID
Tiered Fee: $65.00 ($65.00 <=2" standard)
RPZhigh hazard
Wilkins 975XL · Serial #W975-5531 · 0.75"
Riverfront Cafe & Bakery · 44 Water St, Portland · Basement dry storage near soda carbonators
District: City Water District #4 · Line Pressure: 65 PSI
Assigned Tester: Marcus Vance (BPAT-88412) · Kit: Mid-West 845-5 (#MW-99214)
ASSE 5110 PASSLast Test: Not yet testedNext Due: Sep 27, 2027 (335-day recall)
Check #1 DifferentialFloor: 5.0 PSID
6.8 PSID
Check #2 DifferentialFloor: 1.0 PSID
2.0 PSID
Relief Valve OpeningFloor: 2.0 PSID
2.6 PSID
Tiered Fee: $65.00 ($65.00 <=2" standard)
County Water Utility #2 Route
1 valveAnnual 335d Advance Retest RecallPVBlow hazard
Febco 765 · Serial #FB-10492 · 1.5"
Green Valley Golf Club · 880 Fairway Drive, Portland · Clubhouse south backflow cage behind 9th green
District: County Water Utility #2 · Line Pressure: 65 PSI
Assigned Tester: Marcus Vance (BPAT-88412) · Kit: Mid-West 845-5 (#MW-99214)
ASSE 5110 PASSLast Test: Sep 1, 2026Next Due: Aug 2, 2027 (335-day recall)
Check #1 DifferentialFloor: 1.0 PSID
2.2 PSID
Air Inlet OpeningFloor: 1.0 PSID
1.8 PSID
Relief Valve OpeningFloor: 2.0 PSID
0.0 PSID
Tiered Fee: $65.00 ($65.00 <=2" standard)